IMJ00503 V3E.DOC Page 24 of 40 19.02.2009
For SSI interface operation, the wiring diagram is as follows:
Fig. 5: Wiring for SSI interface operation
4.7 Alarm Outputs
Parameter settings for alarm outputs can be made via Profibus. This function is
only available with the Profibus in active state.
Each of the two alarm outputs allows a given object or state to be monitored for
positive or negative excession of its limit values. This is achieved with the help of a user
definable distance threshold value (AC). Which way the particular alarm output will switch
depends on the mathematical sign of its hysteresis.
Rule:
Positive hysteresis: With increasing distance, the output switches from LOW to
HIGH, as soon as AC + AH/2 is exceeded, with decreasing
distance, it switches from HIGH to LOW, as soon the distance
value falls below AC – AH/2.
Negative hysteresis: With increasing distance, the output switches from HIGH to
LOW, as soon as AC + |AH/2| is exceeded, with decreasing
distance, it switches from LOW to HIGH, as soon the distance
value falls below AC – |AH/2|.
Power Supply
PLC
white
brown
green
yellow
gray
orange
blue
red
black
violet
white/brown
white/black